mA Loop Calibrator, Calog-Loop II
CALOG-Loop II is a handheld calibrator with functions to install and maintain all powered and non-powered milliamp loops. Its small size, rugged design, rubber protective boot, high precision and Li-ion long-lasting rechargeable battery pack makes it ideal for industrial field calibration.
Data may be logged to the removable SD card in CSV format, with user-selectable data fields and timebase. Logged data may also be retrieved via the USB port. CALOG calibrators are made by Instrotech and comply with CE and C-Tick EMC and EMI and Low Voltage directives.
- Small, rugged, handheld with a protective rubber cover
- Graphic display of measured value, percent and battery status
- Measure, source and simulate 0-24 mA with 0.01% accuracy and 1 microamp resolution
- Linear, Flow and Valve stroking functions
- Increment, Step, Auto Step and Ramp modes
- Measure 32V with 0.005% accuracy and 1mV resolution
- Continuity test function
- Trend logging with programmable timebase
- Data logging to removable SD card with time and date
- USB port for access to logged data
- Displays values in mA and % or % and mA
- Programmable auto-off and selectable display resolution
- Lithium-ion rechargeable battery pack with 'fuel gauge' chip
- Carry case, battery charger, SD card, test leads and factory calibration certificate
- 2 year material and workmanship guarantee (excludes batteries)
| Input Ranges | Impedance | Accuracy | Resolution |
| 0 to 24 mA | Input Impedance ±17 Ω 250mA Fused | 0.01 % of FS | 1 µA |
| 0 to 32 V | Input Impedance ±110 kΩ | 0.005 % of FS | 1 mV |
| Continuity | with a less than 100 Ω trigger and 1mA excitation, with visual and audible confirmation | ||
| Output Range | Load | Accuracy | Resolution |
| 0 to 24 mA | Output load max 500 Ω | 0.01 % of FS | 1 µA |
Calog-Loop II mA calibrator
Calog Loop calibrator screens
Calog loop calibrator with case
Calog Loop II functions